光伏调试
一、调试基础 | Commissioning Fundamentals
二、组串级调试 | String-Level Commissioning
三、逆变器调试 | Inverter Commissioning
四、系统级调试 | System-Level Commissioning
String Commissioning — Voc, Isc, and I-V Curve Tracing
He, let's start the string commissioning for Block 2. There are 240 strings in this block — 28 modules each. How are we going to handle the volume?
贺工,我们开始第二区的组串调试。这个区240串——每串28块组件。这么多 量怎么处理?
贺工: We're sampling 10% of strings for full I-V curve tracing — that's 24 strings. For the remaining 90%, we do Voc and Isc only. The I-V curve tracer we're using can do a measurement in about 2 seconds — it's automated, just connect and flash.
我们抽10%做全I-V曲线——24串。其余90%只做Voc和Isc。用的I-V测试仪大 约2秒就能测一组——全自动的,接上就闪测。
测试技术员,从S2-001号串开始。
Test tech, start with String S2-001.
测试技工: S2-001 connected. Voc: 1,410V. The expected Voc at this module temperature of 42°C — adjusting from the STC Voc of 49.5V per module: 28 × 49.5V = 1,386V, corrected for temperature. So 1,410V is within the expected range. Isc: 14.2A — matches the module datasheet adjusted for the current irradiance of 920 W/m².
S2-001接好了。Voc:1,410V。在组件温度42°C下的预期Voc——从每块STC 的Voc 49.5V修正:28×49.5V=1,386V,温度修正后1,410V在预期范围。Isc: 14.2A——匹配组件数据表修正到目前920 W/m²辐照度。
I-V curve: smooth curve, no steps or notches. Fill factor 78.2% — good. Pmax 7.86 kW at operating conditions. String passes.
I-V曲线:光滑曲线、无台阶或缺口。填充因子78.2%——好。运行工况下 Pmax 7.86 kW。这串通过。
What would be a fail condition for the I-V curve?
I-V曲线的失败条件是什么?
贺工: A step or notch in the curve indicates mismatched modules or bypass diode activation — that's a fail. Fill factor below 70% — fail. Pmax more than 5% below the expected value for the irradiance — fail. Any of those and we flag the string for detailed troubleshooting with EL imaging.
曲线出现台阶或缺口——说明组件不匹配或旁路二极管动作——不合格。填充 因子低于70%——不合格。Pmax低于当前辐照度预期值的5%以上——不合格。出 现任何一项我们就标记出来用EL成像做详细排查。
System Commissioning — 72-Hour Reliability Run
贺工,全部单机设备调试完成。并网稳定。现在开始72小时连续可靠性运行 ——商业运行前的最后一步了。通过/不通过的标准是什么?
72小时运行必须连续——任何非计划停运或跳闸都得重新计时。电站必须在 白天时段维持不低于天气修正预期出力的90%平均输出。可用率必须高于99%。
启动72小时计时:周一08:00。记录开始事件。全部逆变器在线——40台上 40台,当前辐照度下总出力72 MW。告警板无报警。
(第1天14:30)刚经历一阵云层——出力跌到28 MW大约15分钟,之后恢复 到81 MW。这是天气原因,不是系统故障——不复位时钟。气象站记录了辐照 度下降,可以关联验证。
(第3天06:45)72小时标记到达。总结:零跳闸、零故障。72小时总发电 量:1,890 MWh。白天平均可用率:99.7%。期间电站性能比:84.2%——在新 组件的预期范围内。
非常好。72小时运行通过。我签署完成证书。这个电站正式进入商业运行。